ALTA Industrial Wireless Duct Temperature Sensor

  • ALTA Industrial Wireless Duct Temperature Sensor

Also Available As:

Information

Format
Frequency
900 MHz
Part#
MNS2-9-IN-TS-DT-L08
Temperature Profile
Probe Length
Power
Antenna
Not Interested?   Return to the Standard Product

The Monnit Wireless Duct Temperature Sensor uses an NTC type thermistor with UL listed plenum cable to accurately measure temperatures in duct work, while maintaining a sealed environment. Can be easily installed and mounted for long term use.

Resellers and OEMs call 1-877-561-4555 to order.

Customers looking for a reseller or more information call 1-801-561-5555.

Product Description

The Monnit Wireless Duct Temperature Sensor uses an NTC type thermistor with UL listed plenum cable to accurately measure temperatures in duct work, while maintaining a sealed environment. Can be easily installed and mounted for long term use.

ALTA - Leading Enterprise Grade "Internet of Things" Solutions

ALTA sensors offer 3 to 4 times the range of standard sensor platforms, extending non-line-of-sight reach to an exceptional 1,000+ feet through walls (12-14 walls typical). Using Frequency-hopping Spread Spectrum (FHSS) also allows ALTA sensors to have better interference immunity from other wireless devices.

Superior power management provides ALTA sensors with almost twice the battery life of Monnit’s standard wireless sensors.

  • Coin cell sensors typically last 3+ years.
  • AA and Industrial sensors typically last up to 10+ years.
ALTA products employ Monnit's new Encrypt-RF™ Security (256-bit Diffie Hellman key exchange and AES-128 CBC encryption for all sensor data messages), so security is maintained at all communication points from sensor to gateway, gateway to software, then back again.

Integrated on-board data storage allows ALTA sensors to store data messages if communication to a wireless gateway is disrupted (power outage, Internet outage, or out of range). Messages that can’t be delivered will be time-stamped and stored in memory (up to the last 512 messages) until communication with the gateway is restored, at which point the messages will all be transmitted.

Over-the-air updates allow ALTA products to be updated remotely if new fixes or features become available.

Monnit ALTA Industrial Sensors come in an IP65, NEMA 4X, CE rated, sealed, and weatherproof enclosure. They are powered by a single, replaceable, Industrial grade 3.6 V battery (included).

An optional solar powered version is also available. The solar powered version includes a Lithium Iron Phosphate rechargeable battery in conjunction with a solar power cell to keep the battery charged and at optimal capacity. If there is no light present at the solar cell, the battery alone could continue to power the sensor for up to 8-10 years.



Product Features

  • Probe temperature range of -40°C to +150°C ( -40°F to +302°F )
  • Accurate to +/- 1° C (+/- 1.8°F)
  • User Calibrated Accuracy +/- 0.25° C (±0.45°F @ 77°F)
  • UL listed plenum probe cable

  * Actual range may vary depending on environment.
** Battery life is determined by sensor reporting frequency and other variables.


What does this wireless sensor's data look like in software?

Monnit duct temperature sensor data view in software

What's in the box?

  • Wireless Sensor
  • Mounting Hardware
  • 3V Industrial Battery (Pre-Installed)
  • SMA Antenna
 

Duct Temperature Sensor Specifications

Probe Operating Temperature Range -40°C to +150°C ( -40°F to +302°F )
Accuracy @ 25°C +/- 1° C (+/- 1.8°F)
User Calibrated Accuracy +/- 0.25° C (±0.45°F @ 77°F)
Time Constant @ 25°C 30 sec
Cable Rating UL listed plenum cable
 

ALTA Industrial Specifications

Supply Voltage 2.0 - 3.8 VDC
Battery Type Replaceable 3.6V, 1800mAH (single AA sized)
Battery Life Up to 10 Year Battery Life.**
Max Operating Temperature -40° to 85°C (-40° to 185°F)
Optimal Battery Operating Temperature +10°C to +50°C (+50°F to +122°F)
Solar Power Option 3.0 VDC Solar Panel
600 mAH Rechargeable Battery (>2000 Charge Cycles - 80% of Initial Capacity)
Charging Temperature Range: 0° to 45°C (32° to 113°F)
Max Temperature Range: -20° to 60°C (-4° to 140°F)
Enclosure Material IP65, NEMA 4X, CE rated, sealed, weatherproof enclosure
UL Rating UL Listed to UL508-4x specifications (File E194432)
Dimension 3.7 in x 2.32 in x 1.38 in
 

ALTA 900 MHz Specifications

Operating Frequency 900 MHz Operating Frequency
Device Range Up to 1,000 ft. non-line-of-sight, wireless device range*
Security Diffie-Hellman Key Exchange + AES-128 CBC
Certifications Complies with Part 15 of the FCC Rules. (FCC ID: ZTL-G2SC1)
Complies with Industry Canada standards. (IC: 9794A-G2SC1)
Specifications Image

Suggested Application Uses for This Sensor

  • Air Duct Temperature Monitoring
  • HVAC Operation & Testing
  • Data Center Monitoring
  • Coolers & Freezers
  • Environmental Monitoring
  • Smart Machines & Smart Structures