The Power-over-Ethernet (PoE) Thermocouple Sensor is available with a hardwired thermocouple or K-type connector to support various thermocouple types and ranges. The hardwired thermocouple option measures temperatures up to 400°C (752°F).
The Power-over-Ethernet (PoE) Sensor products measure various conditions (environmental, power, access). All devices come with flexible settings — including notifications, alerts, reports, and maps — can be customized in the iMonnit online sensor management interface.
No PoE infrastructure in your building? Plug the PoE•X Sensors into your Ethernet network and then power the sensors with the optional AC power supply.
Click here to view all Monnit Power over Ethernet Sensors.
Thermocouple Specifications |
|
Thermocouple Connection Options | 6 ft hardwired probe / 5 ft K-type connector |
K-Type Fixed Probe - Accuracy above 0°C | +/- 2.2°C or 0.75% (whichever is greater) |
K-Type Fixed Probe - Accuracy below 0°C | +/- 2.2°C or 2.0% (whichever is greater) |
K-Type Fixed Probe - Temperature Range | -100°C to +400°C ( -148°F to +752°F ) |
Variation Specifications |
|
Hardware | .10 / 100 Ethernet Controller |
Operation | Full- and Half-Duplex |
Cross-Over Correction | Automatic MDI / MDI-X |
Protocols Supported | DHCP, DNS, NTP, UDP, TCP, SNMP, Modbus TCP |
Cable Connector | RJ45 |
Device Memory | Up to 50,000 sensor messages; varies based on sensor type. (Sensor messages will be stored in the event of Internet outage and transferred when connection is restored.) |
Operating Temperature | -20 to +60°C (-4 to 140°F) |
Storage Temperature: | -40 to +85°C (-40 to 185°F) |
IEEE Standard Compliance | 802.3AF-2003 / 802.3AT-2009 Class 1 |
Input Power | Supplementary Power Requirement |
Lead Wire Length | Type-K, 6 inches long with 1.6 inch by 0.6 inch flange between probe and connection cord |
Weight | 6.32 oz. (179 g.) |